消諧波無功補償裝置
特點
1 補償基波無功,提高功率因數(shù)。
2 過濾一定量的諧波,改善電能質(zhì)量。
3 精確配置電容器和電抗器的比例,避免系統(tǒng)發(fā)生諧振。
4 采用進口交流接觸器對補償支路進行投切。
5 垂直母排系統(tǒng),帶低壓熔斷保護。
6 采用可控硅投切方式,導通無延時,快速補償無功。
7 零電壓投入,零電流切除,投入時不產(chǎn)生涌流,切除時不產(chǎn)生高壓,可在20ms內(nèi)平滑投切。
8 補償基波無功,提高功率因數(shù)。
9 過濾一定量的諧波,改善電能質(zhì)量。
10 采用可控硅投切方式,無涌流,無暫態(tài)過程,響應速度快。
11 垂直母排系統(tǒng),帶低壓熔斷保護。
Harmonic elimination reactive power compensation device
Characteristic
1 compensate fundamental reactive power and improve power factor.
2 filter a certain amount of harmonic to improve the power quality.
3 accurately configure the proportion of capacitors and reactors to avoid system resonance.
4 use the imported AC contactor to switch the compensating branch.
5 vertical bus system with low voltage fuse protection.
6, using SCR switching mode, conduction without delay, quick compensation reactive power.
7 zero voltage input, zero current removal, input does not produce inrush current, when the cut does not produce high voltage, can be in 20ms smooth switching.
8 compensate fundamental reactive power and improve power factor.
9 filter a certain amount of harmonic to improve the power quality.
10 SCR switching mode, no inrush current, no transient process, fast response.
11 vertical bus system with low voltage fuse protection.
技術參數(shù)
1 額定電壓: 400V
2 過 流: 1.7In
3 控制電壓: 230V 50Hz (LBKT 5-15V DC)
4 控制延時: ≤1s (LBKT≤40ms)
5 電抗率誤差: ≤0.3%(絕對值)
6 噪音: 1米距離額定工作下<45db
7 配有溫度控制端子,110~120℃過熱斷開(常閉型)
8 相對濕度: ≤85%
9 最大允許海拔: ≤2000米(5000米可特殊定制)
10 安裝場合:室內(nèi)
11 安裝方式:水平
technical parameter
1 rated voltage: 400V
2 over current: 1.7In
3 control voltage: 230V, 50Hz (LBKT, 5-15V, DC)
4 control delay: = 1s (LBKT = 40ms)
Error: 5 reactance ratio is less than or equal to 0.3% (absolute value)
6 noise: 1 meters distance rated work < 45dB
7, with temperature control terminal, 110~120 degrees overheating shutdown (normally closed)
8 relative humidity: less than 85%
9: the maximum allowable altitude less than 2000 meters (5000 meters can be customized)
10 installation: Indoor
11 installation: Horizontal